GAVH Series Low-Temperature Full Inverter Heat Pump Chilled/Hot Water Unit

Cooling in summer and heating in winter, suitable for areas above -15℃.

The water-side heat exchanger uses a high-efficiency plate heat exchanger. In cooling mode, the refrigerant inlet is equipped with a high-efficiency distributor to ensure more uniform refrigerant distribution.

Advanced variable-frequency drive technology ensures smoother operation of the unit.

Pre-defrost technology prevents ice formation at the bottom of the heat exchanger in winter, ensuring stable heating operation.

Product Advantages

Pre-defrost technology

Prevents ice formation at the bottom of the heat exchanger in winter

Ensures stable heating operation during winter

Normal operation at -15℃

Uses a high-efficiency plate heat exchanger dedicated to hot water, providing superior heat transfer

Suitable for areas above -15℃

More stable and reliable

Pre-defrost technology prevents ice formation at the bottom of the heat exchanger in winter

Ensures stable heating operation during winter

Variable-frequency drive technology

Uses advanced variable-frequency drive technology

Ensures smoother operation of the unit

High-efficiency heat exchange for cooling

The water-side heat exchanger uses a high-efficiency plate heat exchanger

In cooling mode, the refrigerant inlet is equipped with a high-efficiency distributor, ensuring more uniform refrigerant distribution

-15C

Low-temperature operation

Pre-defrost

Technology

High efficiency

Heat exchange + cooling

Multiple protections

Stable and reliable

Quiet

Operation

  • -15C
    -15C
  •  Pre-defrost
    Pre-defrost
  • High efficiency
    High efficiency
  • Multiple protections
    Multiple protections
  •  Quiet
    Quiet

Basic Parameters

Model GAVH 05-Y2P GAVH 08-Y2P GAVH 10-Y2P GAVH 13-Y2P GAVH 16-Y2P GAVH 22-Y3P GAVH 26-Y3P GAVH 31-Y3P GAVH 41-Y3K
Condition: 35℃/24℃
Outlet Water Temperature: 7℃
Rated Cooling Capacity kW 5.1 7.8 10.0 13.0 15.8 21.8 26.0 30.4 40.5
Power kW 1.7 2.7 3.4 4.2 5.3 7.0 9.0 10.0 14.0
COP / 3.0 2.9 2.9 3.1 3.0 3.1 2.9 3.0 2.9
Condition: 7℃/6℃
Outlet Water Temperature: 45℃
Rated Cooling Capacity kW 6.3 9.1 12.0 15.0 18.0 27.7 33.0 34.0 46.0
Power kW 1.8 2.6 2.8 4.3 5.6 8.0 9.7 10.0 13.4
COP / 3.6 3.5 4.3 3.5 3.2 3.5 3.4 3.4 3.4
Condition: -12℃/-14℃
Outlet Water Temperature: 41℃
Rated Cooling Capacity kW 3.9 5.6 7.3 9.6 11.2 21.0 23.0 27.0 30.0
Power kW 1.4 2.0 2.3 3.6 4.4 7.8 8.6 9.7 11.5
COP / 2.8 2.8 3.2 2.7 2.5 2.7 2.7 2.8 2.6
Power Supply / 220V~50Hz 380V 3N~50Hz
Maximum Operating Power kW 2.2 3.5 4.0 6.0 6.6 9.6 11.0 12.0 22.5
Maximum Operating Current A 10.0 16.0 18.2 27.2 30.0 15.4 17.6 19.2 36.0
R410A Refrigerant Charge kg 1.2 1.8 2.3 3.7 3.7 5.5 6.8 7.2 7.2
Water-side Heat Exchanger Rated Water Flow m³/h 0.9 1.3 1.7 2.2 2.7 3.8 4.5 5.2 7.0
Connection Size / G1"Internal Thread G5/4"Internal Thread DN40 Flange
Water-side Pressure Loss kPa 30 45 30 15
Dimensions W×D×H mm 842*375*600 1065*445*863 1100*490*1402 1100*400*1568 1120*413*1545 1300*900*2010
Noise dB(A) ≤48 ≤48 ≤48 ≤50 ≤50 ≤55 ≤55 ≤55 ≤60
Weight kg 32 57 60 120 120 180 200 200 360