GHRD-PF Series Pre-cooling Type Liquid Desiccant Fresh Air Handling Unit

Pre-cooling dehumidification technology, no return air required (still operates efficiently when exhaust air is less than 70% of fresh air).

High-temperature chilled water (14/19°C) pre-cooling combined with heat pump dehumidification for double energy saving, reducing cooling source demand by another 30%.

The pre-cooling section intercepts dust, and the solution section performs deep sterilization, providing high-quality, healthy, and clean fresh air.

Compatible with external cooling/heating sources (chilled water 14/19°C, hot water 40/35°C), offering strong system expandability.

Modular design, easy to operate, low make-up water requirement, and low maintenance cost.

Suitable for scenarios with insufficient or no return air (hospitals, electronics factories) and areas where waste heat can be utilized.

Product Advantages

Applicable Locations

Suitable for scenarios with insufficient or no return air (hospitals, electronics factories)

Areas where waste heat can be utilized

Ultra-High Energy Efficiency

Pre-cooling Dehumidification Technology

High-temperature chilled water pre-cooling combined with heat pump dehumidification for dual energy saving

Deep Purification

Intercepts dust and performs deep sterilization to provide high-quality, clean fresh air

Prevents secondary pollution

Modular Design

Modular design, easy to operate

Supports remote control

COP>5.0

Ultra-High Energy Efficiency

Modular Design

Design

Dynamic Humidity

Control

Salt Solution Inactivates

Microorganisms and Bacteria

-40℃

Anti-Freeze / Does Not Freeze

  • COP>5.0
    COP>5.0
  • Modular Design
    Modular Design
  • Dynamic Humidity
    Dynamic Humidity
  • Salt Solution Inactivates
    Salt Solution Inactivates
  • -40℃
    -40℃

Basic Parameters

Unit Model Unit GHRD-
PF-02
GHRD-
PF-03
GHRD-
PF-04
GHRD-
PF-05
GHRD-
PF-06
GHRD-
PF-08
GHRD-
PF-10
GHRD-
PF-12
GHRD-
PF-15
GHRD-
PF-20
GHRD-
PF-25
Outdoor Air Volume 2000 3000 4000 5000 6000 8000 10000 12000 15000 20000 25000
Cooling Capacity kW 41 62 83 104 124 166 207 249 311 415 518
Dehumidification Capacity kg/h 41 62 82 103 123 164 205 246 308 410 513
Heating Capacity kw 26 39 51 64 77 103 128 154 193 257 321
Humidification Capacity kg/h 13 19 25 32 38 51 63 76 95 126 158
Make-up Water Flow kg/h 15 23 30 38 45 61 76 91 114 152 190
Pre-cooling/heating Coil Chilled Water
Temperature
14/19 14/19 14/19 14/19 14/19 14/19 14/19 14/19 14/19 14/19 14/19
Chilled Water
Flow Rate
m³/h 5.6 8.4 11.2 14 16.8 22.5 28.1 33.7 42.1 42.1 70.2
Hot Water
Temperature
40/35 40/35 40/35 40/35 40/35 40/35 40/35 40/35 40/35 40/35 40/35
Standard
Static Pressure
Hot Water
Flow Rate
m³/h 4.4 6.6 8.8 11 13.3 17.7 22.1 26.5 33.1 44.2 55.0
Pressure Bearing Capacity Mpa 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
Water Resistance kPa 50 50 50 50 50 50 50 50 50 50 50
Connecting Pipe
Size
- DN40 DN50 DN50 DN65 DN65 DN65 DN80 DN80 DN65 DN80 DN80
High Static Pressure Static Pressure
Range
Pa 150-350 150-250 150-200 150-250 150-350 150-500 150-200 150 150-500 150-200 150
Installed
Power
kW 8.44 9.24 10.64 16.11 16.11 27.12 27.12 34.22 54.24 54.24 68.44
Noise dB(A) 60 61-62 62-63 62-64 64 64 65 65-66 67 67-68 68-70
Static Pressure
Range
Pa 400-600 300-600 250-600 300-500 400-600 550-600 250-450 200-600 550-600 250-450 200-600
Installed
Power
kW 8.84 9.94 11.44 16.11 17.11 28.62 28.62 36.22 57.24 57.24 72.44
Noise dB(A) 61 61-62 63 63 64 64-65 65-66 67 68-69 69-71 72
Unit
Dimensions
Length mm 3200 3200 3200 3200 3200 3200 3200 3200 3200 3200 3200
Width mm 1140 1140 1140 1500 1500 2000 2360 2720 5000 5720 6440
Height mm 2600 2600 2600 2800 2800 2800 2800 2800 2800 2800 2800
Operating Weight kg 2330 2430 2530 2740 2840 3620 4400 5200 7240 8800 9900
Ventilation
System
Fan System Centrifugal Fan
Drive Mode Belt Drive / Direct Drive
Filtration Grade Preliminary Efficiency (G4)